Direct loop.  The circulation makes the floor be the radiator.  For a large area, I'm thinking about 180' x 90' it may need supplemention depending on the generator size.

A direct-loop system is the most thermodynamically efficient choice for this application. By treating the 16,200-square-foot factory floor as the primary radiator, you eliminate the energy loss inherent in a heat exchanger and ensure the most immediate transfer of thermal energy from the generator's jacket water to your concrete curing zone.

Given the 180' x 90' footprint, your concern regarding supplementation is a valid engineering consideration. Here is a breakdown of the thermal load and potential ways to bridge the gap.


1. Thermal Load vs. Generator Output

A standard water-cooled diesel or natural gas generator typically rejects approximately 2,500–3,500 BTU per kW of electrical output into the cooling system.


2. Strategic Supplementation Methods

To maintain the Fortress Grade production speed without over-investing in a massive generator, consider these "boost" strategies:


3. Direct Loop Maintenance Considerations

In a direct loop, the water circulating through your floor is the same water cooling your engine.