Dear Review Panel,
Please find enclosed the formal Finite Element Analysis (FEA) report titled "Finite Element Analysis of a Precast Insulated Concrete Wall System," conducted using ANSYS Mechanical APDL, Workbench, and LS-DYNA 2021 R1.
This study evaluates the structural performance of the proprietary modular concrete cavity wall construction system (Cozy Crete System) under gravity loads, thermal bow, a 400 psf design wind pressure/suction envelope, and high-velocity windborne debris impacts per Hurricane and ICC 500 Tornado standards.
Submission Summary & Key Findings
System Configuration: The analysis examines a 12 in. thick wall assembly comprising a 2 in. precast exterior skin, a 4.5 in. polyiso insulation core, a 6.5 in. cast-in-place concrete core (reinforced with vertical and horizontal rebar), a 2 in. precast interior skin, and 1-1/2 in. No. 9 expanded steel lap ties spaced every 12 in. to develop composite action.
- Governing Load Case & Reinforcement Recommendation: Suction governs structural capacity due to limited composite transfer through the steel laps when the exterior skin is in tension. To reliably meet the 400 psf design wind pressure envelope, the specification recommends #4 rebar at 8 in. spacing within the core (yielding a design strength of 420 psf under suction), as wider spacings fall short of the 400 psf threshold.
- Missile Impact Performance (LS-DYNA): Explicit dynamic simulations confirm that the wall successfully withstands both the 9 lb hurricane missile (ASTM E1996) and the 15 lb tornado missile (ICC 500) without perforation or interior face concrete dislodgment.
- Key Design Adjustments Identified:
- Base Dowel Anchorage: FEA results indicate a tensile demand of ~5,430 lb per #4 dowel under 400 psf wind loading. Standard 2 in. adhesive embedment is insufficient; a minimum 7.0 in. embedment within an 8.25 in. (or thicker) foundation slab/footing is recommended.
- Thermal Stress Management: Winter thermal gradients induce localized tensile stresses along the top lap edge of exterior panels, pointing to the need for appropriate joint detailing or elastomeric sealants.
Review Objectives
We invite your rigorous engineering review, audit of the boundary conditions, and verification of the FEA modeling methodology, particularly concerning:
- The load-slip behavior modeled for the expanded steel laps across the insulation layer.
- The dynamic material damage parameters utilized for the concrete and polyiso components under debris impact.
- The base connection uplift mechanics and recommended dowel embedment lengths.
We welcome your feedback and look forward to discussing your findings and recommendations.
Sincerely,
Walter DeVore
Independent Inventor & Developer